Mercury 230 AR
APPLICATION
The meters are designed for single-tariff measurement of active and reactive electric energy and power, as well as electrical parameters in three-phase three- and four-wired AC networks with subsequent accumulated data storage and transfer to the AMR/AMI system’s data collection centers.
The meters are designed for indoor operation and can be installed in the areas with additional environmental protection (installed inside premises, cabinets or boards).
MODIFICATIONS
The meter modifications are available with different rated voltage, rated and peak current, and additional functionalities which are not related to metrological perfomance.
Metrological performance
Meter accuracy class (active/reactive) |
|
• transformer connection | 0.5S / 1 |
• direct connection | 1 / 2 |
Rated voltage, V |
|
• CT&VT connection | 3*57,7 / 100 |
• CT, direct connections | 3*230 / 400 |
Base/peak current, A |
|
• CT, CT&VT connections | 5 / 7.5 |
• direct connection | 5 / 60; 10 / 100 |
Peak current for direct connection meters during 10 ms | 30*I max |
Peak current for CT, CT&VT connection meters during 0.5 s | 20*I max |
Starting current, А |
|
• CT, CT&VT connections | 0.005 |
• direct connection | 0.02; 0.04 |
REGULATORY COMPLIANCE
GOST R 52320, GOST R 52322, GOST R 52323, GOST R 52425. State registers of Russia and CIS countries.
Active/total power consumption in each meter voltage circuit at rated voltage, W/V*A | 1.5 / 9 |
Total power consumed by each current circuit, max, V*А | 0.1 |
Data retention during power outage, min, years | 10 |
Calibration interval, years | 10 |
Warranty period, years | 3 |
Mean time between failures, min, h | 150,000 |
Operating temperature range, °C | -40 to +55 |
Weight, max, kg | 1.5 |
Dimensions (LхWхH), mm | 170x74x258 |
— The meter measures, stores, displaying on LCD and communicate information via different interfaces of active and reactive electrical energy:
— Energy measurement independently from current circuits phasing (measurement per module).
— Measurement of electrical network parameters:
- instantaneous values of active, reactive and total power for each phase and for the sum of all phases with the total power vector direction indication;
- RMS of phase currents and voltages;
- phase angles;
- power frequency;
- power factors of each phase and of their sum.
— Multifunc tional pulse output including a load control function.
— Automatic self-diagnostics with error indication.
Table of commercially available meters modifications. Other modifications are available on request.
Modification | Rated voltage, V | Nominal/ maximum current, А | Accuracy A/R | Interfaces, relay |
---|---|---|---|---|
Mercury 230 АR-00 R | 3*57,7/100 | 5(7,5) | 0,5S/1,0 | RS-485 |
Mercury 230 АR-01 R | 3*230/400 | 5(60) | 1,0/2,0 | RS-485 |
Mercury 230 АR-02 R | 3*230/400 | 10(100) | 1,0/2,0 | RS-485 |
Mercury 230 АR-03 R | 3*230/400 | 5(7,5) | 0,5S/1,0 | RS-485 |
Mercury 230 АR-01 CL | 3*230/400 | 5(60) | 1,0/2,0 | CAN, PLС-I |
Mercury 230 АR-02 CL | 3*230/400 | 10(100) | 1,0/2,0 | CAN, PLС-I |
Mercury 230 АR-03 CL | 3*230/400 | 5(7,5) | 0,5S/1,0 | CAN, PLС-I |
Meter modification code structure:
Mercury 230 AR-0X R (C L)
А – active energy measurement,
R – reactive energy measurement,
0Х – code of rated/peak current and voltage, accuracy class,
Rated/peak currents, voltages and accuracy classes
Code | Rated (peak) current, A | Rated voltage, V | Code Accuracy class |
00 | 5/10 | 3 x 57.7/100 | 0.2S/0.5 or 0.5S/1 |
01 | 5/60 | 3 x 230/400 | 1/2 |
02 | 5/100 | 3 x 230/400 | 1/2 |
03 | 5/10 | 3 x 230/400 | 0.2S/0.5 or 0.5S/1 |
Have questions?